| Plan Review Notes For Permit 99051209 |
| Permit Number |
99051209 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | NEED FAULT CURRENT CALCULATIONS AND | | | AIC RATING TO BE DRAWN ON PANEL SCHEDULE | | | AS PER ART.215-5 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:2`6`12`RULE 210-52A OUTLET | | | REQ`MENTS/SPACING. | | | | | | PLEASE HAVE FIRST TWO SUBMITTED BEFORE | | | ROUGH INSPECTION. |
|