| 2001-01-08 00:00:00 | SHT A2.1-AN ADD'L.HANDICAP STALL IS |
| | REQ'D.IN ROOM#113 PER F.A.C.B.C.SEC. |
| | 4.22.4. |
| | |
| | COMMON LAUNDRY AREAS SHALL COMPLY W/ |
| | F.A.C.B.C. SEC.4.1.6.9 (1)(B),4.27.1. |
| | |
| | HANDICAP SHOWERS AND SEATS SHALL COMPLY |
| | W/F.A.C.B.C. SEC.4.21.2, 4.21.3. |
| | |
| | SHT.A7.2-ELEV.#8-HANDICAP URINAL SHALL |
| | COMPLY W/F.A.C.B.C.SEC.4.18.2 (MAX.17" |
| | A.F.F.) |
| | |
| | SHT.A7.3-ADDITIONAL H.C. STALL REQ'D. |
| | IN MEN'S AND WOMEN'S RESTROOMS PER |
| | F.A.C.B.C. SEC.4.22.4.**(NOTE:CHECK ALL |
| | RESTROOMS FOR THIS REQ'.) |
| | |
| | SHT.A7.3-ELEV.#19-H.C URINAL SHALL BE |
| | AT MAX.17" A.F.F.TO RIM PER F.A.C.B.C. |
| | SEC.4.18.2. |
| | |
| | FLOOR DRAINS SHALL NOT EXCCED DISTANCE |
| | FROM VENT PER SPC.SEC.908 & TABLE 908.1 |
| | |
| | MAX.TEMPERATURE OF WATER DISCHARGED TO |
| | SANITARY SYSTEM SHALL NOT EXCEED 140 |
| | DEGREES.SPC.SEC.807.3 |
| | |
| | MAX.TEMPERATURE TO RESTROOMS SHALL NOT |
| | EXCEED 110 DEGREES PER FLA.ENERGY CODE |
| | SEC.412.ABCD.2.3.2. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | SEC.610.4.1, 610.4.2. |
| | |
| | FLOOR DRAINS ARE NOT PROPERLY VENTED. |
| | COMPLY W/SPC SEC.901.2, TABLE 908.1 |
| | |
| | SUBMIT STORM RISER DIAGRAM FOR THE |
| | STORM DRAINAGE SYSTEM.SPC 104.2.1. |
| | |
| | SUBMIT MANUF.SHEETS FOR GASEQUIPMENT. |
| | EQUIPMENT SHALL BE LISTED PER STD.GAS |
| | CODE SEC.402.1. |
| | |
| | CLEARLY SHOW WATER SOURCE FOR IRRIGATION |
| | SYSTEM .BACKFLOW PREVENTION DEVICE IS |
| | REQ'D.IF ON CITY WATER.SPC 601.6 |
| | |
| | EQUIPMENT SUPPLY LINES ON GAS HEADER ARE |
| | UNDERSIZED.COMPLY W.STD.GAS CODE SEC. |
| | 305.2(INDICATE TYPE OF PIPING TO BE |
| | INSTALLED.)AND TABLES 305.4. |
| | |
| | SUBMIT CALCULATIONSFOR ROOF DRAINAGE |
| | OVERFLOW.COMPLY W/SBC SEC.1507.4.3, |
| | 1604.6.2.,STD.PLBG.CODE SEC.1109. |
| | |
| | SUPPLY OCCUPANT LOAD AS DETERMINED BY |
| | SPC SEC.407.1.3 TO ENSURE COMPLIANCE |
| | FOR MINIMUM FIXTURE REQUIREMENTS. |