Plan Review Notes
Plan Review Notes For Permit 99051162
Permit Number 99051162
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00OVER 4 FIXTURE UNITS INSTALLED ON WET
 VENT. SPC SEC.911.1(1).
  
 VENTING OF 2 WATER CLOSETS SHALL COMPLY
 W/SEC.911.1.3 OF COUNTYWIDE AMENDMENTS
 TO STANDARD PLBG.CODE.(SEE BATH #3 &
 POWDER ROOM.)