Plan Review Notes
Plan Review Notes For Permit 99051159
Permit Number 99051159
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENTRY DOORS CAN'T HAVE STORM PANELS
 BECAUSE THE MAIN EGRESS OF THE HOUSE
 WILL BE BLOCKED. REVISE STORM PANELS
 INSTALLATION SCHEDULE AS REQUIRED.
 2-ARCHITECT SPECIFIED GIRDER TRUSS AT
 FRONT PORCH. SPECIFY UPLIFT CONNECTORS.
 *PROVIDE COMPLETE SPECIFICATIONS FOR
 DETAIL B-6.
 *REVISE CONNECTOR C-A6 AS REQUIRED IN
 ORDER TO RESIST THE UPLIFT LOADS
 CALCULATED ON ENGINEERED TRUSSES.
 3-ENGINEERED TRUSS LAYOUT DON NOT SHOW
 GIRDER TRUSS AT FRONT PORCH SPECIFIED
 BY ARCHITECT. REVISE AS REQUIRED.
 *TRUSS DRAWINGS NEED TO BE UPDATED TO
 ASCE 7-95.
 CUTTING AND PASTING ENGINEERED TRUSSES
 WILL NOT BE ACCEPTED.
 4-REVISED ORIGINAL DRAWINGS SHOWING THE
 CORRECTIONS/CLARIFICATIONS.
 5-SLIDING GLASS DOORS:
 *USE ONLY THE REINFORCED DOORS IN ORDER
 TO MEET THE DESIGN PRESSURES SPECIFIED
 BY THE ARCHITECT.
 *PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS ASSEMBLY W/ TRANSOM ABOVE.
 6-MINIMUM CLEAR OPENING AT BEDROOM
 WINDOWS TO BE 5.0 S.F AS PER SECTION
 1005.4.4 SBC 1997. PROVIDE THE EXACT
 DIMENSIONS FOR WINDOWS AT BEDROOM #2 TO
 VERIFY CLEAR OPENING PRIOR TO
 INSTALLATION.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS PRIOR TO INSTALLATION.
 8-GARAGE DOOR PRODUCT APPROVAL DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY
 ARCHITECT. UPGRADE GARAGE DOORS.