2001-01-08 00:00:00************PROVISO********************
  
 NEED TO SUBMIT PLANS WITH FAULT CURRENT
 CACULATIONS/FOR AIC RATING.215-5
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM FIRST MEANS OF DISC. TO
 PANEL.250-92/250-95
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 SYSTEM TO BLDG.STEEL ALSO.
  
 NEED THE ABOVE INFORMATION SUBMITTED
 BEFORE ROUGH INSPECTION.