2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-REVISE MEAN ROOF HEIGHT. THERE IS ONLY
 ONE MEAN ROOF HEIGHT FOR THE ENTIRE
 BUILDING. FOOTNOTES AT TABLE 1606.2A
 SBC 1994.
 MEAN ROOF HEIGHT IS 24'-0" PLUS OR
 MINUS. SEE ARCHITECT'S DRAWINGS.
 2-THERE ARE SLIGHT VARIATIONS ON TRUSS
 LAYOUT AND ARCHITECT'S FRAMING PLANS.
 PROVIDE THE SPECIFIC CONNECTORS AS
 REQUIRED. SEE COMMENTS ON TRUSS LAYOUT
 3-ARCHITECT TO REVISE AND SPECIFY ALL
 HURRICANE CONNECTORS THAT WILL RESIST
 THE UPLIFT LOADS CALCULATED ON
 ENGINEERED TRUSSES. NOTE THAT THERE
 ARE SOME CONNECTORS THAT NEED TO BE
 UPGRADED IN ORDER TO RESIST THOSE
 LOADS. EG: SEE TRUSS B9 ENGINEERED
 CALCULATIONS AND CONNECTORS SPECIFIED.