Plan Review Notes
Plan Review Notes For Permit 99051033
Permit Number 99051033
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************PROVISO*********************
  
 NEED TO SUBMIT PLANS WITH FAULT CURRENT
 CALCULATIONS/AND AIC RATING DRAWN ON
 PANEL SCHED.ART.215-5
 NOTE:MISSING LIGHT OUTSIDE GARAGE BACK
 DOOR.ART.210-70 MEANS OF EGRESS.
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 SPACE ARE TO BE GFI.ART210-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS AND ROOMS OPT./TO BE
 BEDROOMS.
 NOTE:MISSING RECEPT.REQ`D FOR A/C
 COND.UNIT ART.210-63
 NOTE:RECEPTS.REQ`D IN HALLS AS PER
 ART.210-52H
 NOTE:MANY MISSING RECEPTS.REQ`D AS PER
 ART.210-52A 2`6`12`RULE.
 NOTE:EQUIPMENT GROUNDING COND.REQ`D
 FROM MAIN DISCONNECT TO PANELS AS PER
 ART.250-92/250-95
 NOTE:GROUNDING ELECTRODE SYSTEM TO
 GRND.ROD,BLDG.STEEL.
  
 NEED TO HAVE ALL THE ABOVE INFORMATION
 BEFORE ROUGH INSPECTION.!!!