| Plan Review Notes For Permit 99051033 |
| Permit Number |
99051033 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************PROVISO********************* | | | | | | NEED TO SUBMIT PLANS WITH FAULT CURRENT | | | CALCULATIONS/AND AIC RATING DRAWN ON | | | PANEL SCHED.ART.215-5 | | | NOTE:MISSING LIGHT OUTSIDE GARAGE BACK | | | DOOR.ART.210-70 MEANS OF EGRESS. | | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | | SPACE ARE TO BE GFI.ART210-8-A-6 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS AND ROOMS OPT./TO BE | | | BEDROOMS. | | | NOTE:MISSING RECEPT.REQ`D FOR A/C | | | COND.UNIT ART.210-63 | | | NOTE:RECEPTS.REQ`D IN HALLS AS PER | | | ART.210-52H | | | NOTE:MANY MISSING RECEPTS.REQ`D AS PER | | | ART.210-52A 2`6`12`RULE. | | | NOTE:EQUIPMENT GROUNDING COND.REQ`D | | | FROM MAIN DISCONNECT TO PANELS AS PER | | | ART.250-92/250-95 | | | NOTE:GROUNDING ELECTRODE SYSTEM TO | | | GRND.ROD,BLDG.STEEL. | | | | | | NEED TO HAVE ALL THE ABOVE INFORMATION | | | BEFORE ROUGH INSPECTION.!!! |
|