Plan Review Notes
Plan Review Notes For Permit 99050910
Permit Number 99050910
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) AIR BALANCE SCHEDULE REQUIRED TO
 COMPLY WITH SMC 1994 501.2
 3) FIRE DAMPERS REQUIRED AT ALL RATED
 WALL PENETRATIONS
 4) RETURN AIR REQUIRED FROM ALL AREAS W/
 300 CFM OR GREATER SUPPLY AIR