| Plan Review Notes For Permit 99050882 |
| Permit Number |
99050882 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | NEED AIC RATING SUBMITTED ON PLANS. | | | ART.215-5 | | | NOTE:GROUNDING ELECTRODE CONDUCTOR TO | | | BLDG.STEEL ALSO. | | | | | | NEED THE ABOVE BEFORE ROUGH INSPECTION. |
|