Plan Review Notes
Plan Review Notes For Permit 99050881
Permit Number 99050881
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW FIXTURE CLEARANCES OF WATER
 CLOSET AND BIDET FROM WALLS AND CENTER-
 TO-CENTER MEASUREMENTS.S.P.C.SEC. 403.4
  
 BIDET DOWNSTREAM OF W.C.SHALL BE VENTED
 PER S.P.C.SEC. 913.2.
  
 SHWR.IN CABANA BATH IS NOT VENTED
 CORRECTLY.S.P.C. SEC.901.2
  
 W.C.IN CABANA BATH EXCEEDS ALLOWABLE
 DISTANCE FROM VENT PER COUNTYWIDE
 AMENDMENTS TO STANDARD PLBG.CODE SEC.
 908.1,FOOTNOTE #2.
  
 ISOMETRIC SHOWS W.C.'S DRAINING INTO 2"
 LINE.COMPLY W/S.P.C.SEC.AND TABLE 714.2
 FOOTNOTE #5.
  
 CLEANOUTS SHALL BE INSTALLLED PER S.P.C.
 SEC.710.2.1.