2001-01-08 00:00:00****************PROVISO*****************
  
 NEED FAULT CURRENT CALCULATIONS DONE
 FOR AIC RATING WHICH NEED TO BE ON PLANS
 ART.215-5
 NOTE:GROUNDING ELECTRODE COND.TO
 BLDG.STEEL ALSO.
  
 NEED INFORMATION BEFORE ROUGH .