| Plan Review Notes For Permit 99050869 |
| Permit Number |
99050869 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | NEED CALCULATIONS DONE FOR AIC RATING | | | WHICH NEEDS TO BE DRAWN ON PANEL SCHD. | | | ART.215-5 | | | NEED RISER DIAGRAM TO SHOW GROUNDING | | | ELECTRODE CONDUCTOR DRAWN TO GROUND ROD, | | | C.W.P.,AND BLDG.STEEL.215-5 | | | NOTE:NEED EQUIPMENT GROUNDING COND. | | | DRAWN ON PLANS FROM MAIN DISC.TO | | | PANEL AND FROM PANEL TO OTHER DISC.S | | | 250-92/250-95 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE | | | AND OUTSIDE BEDROOMS. | | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | | TOPS ARE TO BE DRAWN GFI/GFI PROTECTED. | | | ART.210-8-A-6 | | | NOTE:MASTER BEDROOM HALL 210-52H | | | NOTE:2`6`12`RULE 210-52A | | | | | | NEED TO SUBMIT BEFORE ROUGH INSPECTION!! |
|