| Plan Review Notes For Permit 99050773 |
| Permit Number |
99050773 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO 2ND.TIME********** | | | | | | NOTE:SUBMIT!!!!PLANS WITH NEW PANEL | | | SCHEDULEWITH AIC RATING OF EQUIPMENT!! | | | NOTE:RISER DIAGRAM NEEDS TO SHOW WIRE | | | SIZES.!! | | | NOTE:GROUDING ELECTRODE SYSTEM NEEDS TO | | | GO TO C.W.P. | | | NOTE: ALL THE ABOVE AS PER ART.215-5 | | | | | | ALL THE ABOVE NEEDS TO BE SUBMITTED | | | AND APPROVED BEFORE ROUGH INSPECTION IS | | | CALLED IN. |
|