2001-01-08 00:00:00SAN.ISOMETRIC DOESN'T MATCH FLOOR PLAN.
 SPC SEC.104.2.1.
  
 CLARIFY LOCATION OF VENT ON WATER CLOSET
 COMPLY W/SPC 901.2,& SEC.911.1.1 OF
 COUNTYWIDE AMEND.TO SPC.1994.
  
 2ND FLR.BATHROOM GROUP CANNOT DISCHARGE
 INTO 1ST.FLR.STACK VENT. SPC SEC.904.1,
 911.4.
  
 SHT.A-14-PLBG.NOTES #3-MIN.SLOPE OF PIPE
 SHALL COMPLY W/SPC SEC.705.
  
 REMOVE TRAPS FROM WATER CLOSETS.
 SPC SEC.1001.6,1001.8.