| Plan Review Notes For Permit 99050607 |
| Permit Number |
99050607 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SAN.ISOMETRIC DOESN'T MATCH FLOOR PLAN. | | | SPC SEC.104.2.1. | | | | | | CLARIFY LOCATION OF VENT ON WATER CLOSET | | | COMPLY W/SPC 901.2,& SEC.911.1.1 OF | | | COUNTYWIDE AMEND.TO SPC.1994. | | | | | | 2ND FLR.BATHROOM GROUP CANNOT DISCHARGE | | | INTO 1ST.FLR.STACK VENT. SPC SEC.904.1, | | | 911.4. | | | | | | SHT.A-14-PLBG.NOTES #3-MIN.SLOPE OF PIPE | | | SHALL COMPLY W/SPC SEC.705. | | | | | | REMOVE TRAPS FROM WATER CLOSETS. | | | SPC SEC.1001.6,1001.8. |
|