Plan Review Notes
Plan Review Notes For Permit 99050548
Permit Number 99050548
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********DENIED****6-11-99***********
  
 NEED TO SUBMIT PLANS WITH THE FOLLOWING!
 1)TOTAL RISER DIAGRAM TO INCLUDE ALL
 OF THE FOLLOWING.
 METER,MAIN DISC.(IF ONE IS BEING USED),
 PANEL,ALL CONDUITS BETWEEN,ALL WIRE
 SIZES.
 2)NEED TO HAVE LOAD CACULATIONS DONE
 AND DRAWN ON PLANS.
 3)NEED PANEL SCHD.WITH AIC RATING
 DRAWN IN.
 4)NEED FAULT CURRENT CALCULATIONS DONE
 FOR AIC RATING.
 5)GROUNDING ELECTRODE SYSTEM ON RISER
 DIAGRAM.CONDUCTOR TO GRND.ROD,CWP+
 BLDG.STEEL.
 ALL THE ABOVE INFORMATION IS REQ`D BY
 ART.215-5
 NOTE:ALSO RECEPT.REQ`D FOR A/C COND.
 UNIT 210-63
 NOTE:2`6`12` ART.210-52A
  
 NEED ALL THE ABOVE INFORMATION.