| Plan Review Notes For Permit 99050548 |
| Permit Number |
99050548 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED****6-11-99*********** | | | | | | NEED TO SUBMIT PLANS WITH THE FOLLOWING! | | | 1)TOTAL RISER DIAGRAM TO INCLUDE ALL | | | OF THE FOLLOWING. | | | METER,MAIN DISC.(IF ONE IS BEING USED), | | | PANEL,ALL CONDUITS BETWEEN,ALL WIRE | | | SIZES. | | | 2)NEED TO HAVE LOAD CACULATIONS DONE | | | AND DRAWN ON PLANS. | | | 3)NEED PANEL SCHD.WITH AIC RATING | | | DRAWN IN. | | | 4)NEED FAULT CURRENT CALCULATIONS DONE | | | FOR AIC RATING. | | | 5)GROUNDING ELECTRODE SYSTEM ON RISER | | | DIAGRAM.CONDUCTOR TO GRND.ROD,CWP+ | | | BLDG.STEEL. | | | ALL THE ABOVE INFORMATION IS REQ`D BY | | | ART.215-5 | | | NOTE:ALSO RECEPT.REQ`D FOR A/C COND. | | | UNIT 210-63 | | | NOTE:2`6`12` ART.210-52A | | | | | | NEED ALL THE ABOVE INFORMATION. |
|