| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT MANUF.VERIFICATION OF PH OF |
| | EFFLUENT FROM FILM PROCESSOR. SPC SEC. |
| | 801.4 |
| | SUBMIT MANUF.DATA SHEETS ON ALL MAKES/ |
| | MODELS OF BACKFLOW PREVENTION DEVICES TO |
| | BE INSTALLED.SPC SEC.601.2,601.6,606.1 |
| | 606.2 |
| | SINK IN STAFF LOUNGE SHALL COMPLY W/ |
| | FLA.ACC.CODE FOR BLDG.CONST.SECS.4.24.1 |
| | THRU 4.24.7 |
| | SUBMIT FIRE SAFING DETAIL AND ASSEMBLY |
| | NO.FROM RECOGNIZED LISTING AGENCY. |
| | SPC 104.2.4 |
| | WATER FILTER SYSTEM SHALL BE NSF |
| | APPROVED.SPC SEC.615.1 |
| | SUBMIT MANUF.INSTALLATION INSTRUCTIONS |
| | AND DATA SHEETS ON X-RAY PROCESSOR, |
| | F.S.C.UNITS,DENTAL CHAIRS,MODEL TRIMMER, |
| | PLASTER TRAP,VACUUM PUMP,AIR COMPRESSOR, |
| | AND ALL OTHER RELATED EQUIPMENT PER SPC |
| | SECS.104.2.1 & NFPA 99-C(1993 ED.) |
| | SHT.P-1.-DETAILS FOR MODEL TRIMMER,FSC |
| | UNITS & PLASTER TRAP SHALL BE LEGIBLE. |
| | SPC SEC.104.2.1 |
| | SHT.P-1.-NOTE #B-9.-"M" COPPER IS NOT |
| | PERMITTED U/G PER COUNTYWIDE AMEND.ORD.# |
| | 3004-96.SEC.611.3. |
| | SHOW HOW WATER PIPING SYSTEM WILL BE |
| | PROTECTED FROM HAZARD & NOISE PER SPC |
| | SEC 607.8.1-607.8.3 |
| | SHT.P-1.-NOTE #D-15.-DRAINAGE MATERIALS |
| | SHALL COMPLY W/SPC SEC.703.1 & TABLE 703 |
| | HORIZ.PIPING SHALL BE SUPPORTED PER SPC |
| | 310.3. |
| | CLEARLY SIZE THE WATER RISER IN IT'S |
| | ENTIRETY.SPC 104.2.1.,607.1,607.2. |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | 610.1,610.4.1. |
| | FSC UNIT DRAINS SHALL BE TRAPPED PER SPC |
| | SEC.401.4 |
| | SLOPE OF DRAINAGE PIPING TO COMPLY W/SPC |
| | 705.2-705.4. |
| | CLEARLY NOTE OCCUPANT LOAD ON PLANS FOR |
| | DETERMINATION OF MIN.REQ'D.SANITARY |
| | FACILITIES.SPC SEC.407.1 THRU 407.2.2. |
| | |
| | *****************PROVISO**************** |
| | A LETTER IS REQ'D.FROM THE MANUF. OF |
| | HE X-RAY PROCESSOR VERIFYING THE PH |
| | OF THE EFFLUENT WILL BE WITHIN THE |
| | ACCEPTABLE RANGE OF 5 AND 10 PRIOR TO |
| | THE INSTALLATION OF EQUIPMENT.6/25/99. |