Plan Review Notes For Permit 99050442
Permit Number 99050442
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT MANUF.VERIFICATION OF PH OF
 EFFLUENT FROM FILM PROCESSOR. SPC SEC.
 801.4
 SUBMIT MANUF.DATA SHEETS ON ALL MAKES/
 MODELS OF BACKFLOW PREVENTION DEVICES TO
 BE INSTALLED.SPC SEC.601.2,601.6,606.1
 606.2
 SINK IN STAFF LOUNGE SHALL COMPLY W/
 FLA.ACC.CODE FOR BLDG.CONST.SECS.4.24.1
 THRU 4.24.7
 SUBMIT FIRE SAFING DETAIL AND ASSEMBLY
 NO.FROM RECOGNIZED LISTING AGENCY.
 SPC 104.2.4
 WATER FILTER SYSTEM SHALL BE NSF
 APPROVED.SPC SEC.615.1
 SUBMIT MANUF.INSTALLATION INSTRUCTIONS
 AND DATA SHEETS ON X-RAY PROCESSOR,
 F.S.C.UNITS,DENTAL CHAIRS,MODEL TRIMMER,
 PLASTER TRAP,VACUUM PUMP,AIR COMPRESSOR,
 AND ALL OTHER RELATED EQUIPMENT PER SPC
 SECS.104.2.1 & NFPA 99-C(1993 ED.)
 SHT.P-1.-DETAILS FOR MODEL TRIMMER,FSC
 UNITS & PLASTER TRAP SHALL BE LEGIBLE.
 SPC SEC.104.2.1
 SHT.P-1.-NOTE #B-9.-"M" COPPER IS NOT
 PERMITTED U/G PER COUNTYWIDE AMEND.ORD.#
 3004-96.SEC.611.3.
 SHOW HOW WATER PIPING SYSTEM WILL BE
 PROTECTED FROM HAZARD & NOISE PER SPC
 SEC 607.8.1-607.8.3
 SHT.P-1.-NOTE #D-15.-DRAINAGE MATERIALS
 SHALL COMPLY W/SPC SEC.703.1 & TABLE 703
 HORIZ.PIPING SHALL BE SUPPORTED PER SPC
 310.3.
 CLEARLY SIZE THE WATER RISER IN IT'S
 ENTIRETY.SPC 104.2.1.,607.1,607.2.
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.1,610.4.1.
 FSC UNIT DRAINS SHALL BE TRAPPED PER SPC
 SEC.401.4
 SLOPE OF DRAINAGE PIPING TO COMPLY W/SPC
 705.2-705.4.
 CLEARLY NOTE OCCUPANT LOAD ON PLANS FOR
 DETERMINATION OF MIN.REQ'D.SANITARY
 FACILITIES.SPC SEC.407.1 THRU 407.2.2.
  
 *****************PROVISO****************
 A LETTER IS REQ'D.FROM THE MANUF. OF
 HE X-RAY PROCESSOR VERIFYING THE PH
 OF THE EFFLUENT WILL BE WITHIN THE
 ACCEPTABLE RANGE OF 5 AND 10 PRIOR TO
 THE INSTALLATION OF EQUIPMENT.6/25/99.