Plan Review Notes
Plan Review Notes For Permit 99050128
Permit Number 99050128
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00*************DENIED********************
  
  
 1)NOTE:AS PER ART:215-5 PANEL SCHEDULE
 TO SHOW BOTH A/C UNITS AND TO SHOW BATH
 GFI CIRCUT WHICH IS REQ`D BY ART:210-52D
 2)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SHOW AIC RATING OF MAINS AND BRANCH
 BREAKERS. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
 3)NOTE:AS PER ART:250-81 NED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 BLDG. STEEL OF NEW ADDITION AND TO GRND.
 ROD.
 4)NOTE:AS PER ART;215-5 PLEASE GIVE
 BETTER DISCRIPTION OF RISER DIAGRAM
 PERTAINING TO 2ND.METER AND 100 AMP
 PANEL.????
 5)NOTE:AS PER 1996 NFPA-72 SMOKE
 DETECTORS NEED TO BE IN AREA OUTSIDE
 BEDROOM.SEE PLANS RELOCATING 1 SMOKE DEC
 INTO HALL FROM LIVING ROOM. ALSO OTHER
 TWO SMOKE DETECTOR THAT ARE CIRCLED ARE
 NOT REQ`D BUT ARE ALLOWED TO BE
 INSTALLED.
 6)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 7)NOTE;AS PER ART:210-52-C-3 REQ`MENTS
 FOR OUTLET SPACING ON PENINSULAR.
 8)NOTE:AS PER ART:210-52 OUTLET SPACING
 INSIDE BEDROOM AS REQ`D FOR THE 2`6`12`
 RULE.
  
 PLEASE HAVE ALL THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL.