| 2001-01-08 00:00:00 | *************DENIED******************** |
| | |
| | |
| | 1)NOTE:AS PER ART:215-5 PANEL SCHEDULE |
| | TO SHOW BOTH A/C UNITS AND TO SHOW BATH |
| | GFI CIRCUT WHICH IS REQ`D BY ART:210-52D |
| | 2)NOTE:AS PER ARTS:110-9/215-5 NEED TO |
| | SHOW AIC RATING OF MAINS AND BRANCH |
| | BREAKERS. AIC RATING IS FIGURED FROM |
| | FAULT CURRENT CALCULATIONS. |
| | 3)NOTE:AS PER ART:250-81 NED TO SHOW |
| | GROUNDING ELECTRODE CONDUCTOR GOING TO |
| | BLDG. STEEL OF NEW ADDITION AND TO GRND. |
| | ROD. |
| | 4)NOTE:AS PER ART;215-5 PLEASE GIVE |
| | BETTER DISCRIPTION OF RISER DIAGRAM |
| | PERTAINING TO 2ND.METER AND 100 AMP |
| | PANEL.???? |
| | 5)NOTE:AS PER 1996 NFPA-72 SMOKE |
| | DETECTORS NEED TO BE IN AREA OUTSIDE |
| | BEDROOM.SEE PLANS RELOCATING 1 SMOKE DEC |
| | INTO HALL FROM LIVING ROOM. ALSO OTHER |
| | TWO SMOKE DETECTOR THAT ARE CIRCLED ARE |
| | NOT REQ`D BUT ARE ALLOWED TO BE |
| | INSTALLED. |
| | 6)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS |
| | SERVING KITCHEN COUNTER SPACE ARE TO BE |
| | GFI/GFI PROTECTED. |
| | 7)NOTE;AS PER ART:210-52-C-3 REQ`MENTS |
| | FOR OUTLET SPACING ON PENINSULAR. |
| | 8)NOTE:AS PER ART:210-52 OUTLET SPACING |
| | INSIDE BEDROOM AS REQ`D FOR THE 2`6`12` |
| | RULE. |
| | |
| | PLEASE HAVE ALL THE ABOVE SUBMITTED FOR |
| | REVIEW AND APPROVAL. |