| Plan Review Notes For Permit 99050128 |
| Permit Number |
99050128 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED********************** | | | | | | NEED COMPLETE SQUARE FOOTAGE CALCULATION | | | SQ.FT. BEING ADDED DOES NOT MATCH | | | APPLICATION WITH PRINTS.!!!!! | | | NOTE:SERVICE GROUNDING ELECTRODE SYSTEM. | | | NOTE:NEED FAULT CURRENT CACULATIONS | | | FOR AIC RATING.215-5 | | | NOTE:NEED NEUTRAL COND. FROM METERCAN | | | TO DISC.TO PANEL. | | | NOTE:REQ`MENTS FOR KITCHEN RECEPTS. | | | 210-8-A-6/210-52C-1-2-3-4-5 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:REQ`MENTS FOR OUTLET SPACING 210-52 |
|