2001-01-08 00:00:00***********DENIED**********************
  
 NEED COMPLETE SQUARE FOOTAGE CALCULATION
 SQ.FT. BEING ADDED DOES NOT MATCH
 APPLICATION WITH PRINTS.!!!!!
 NOTE:SERVICE GROUNDING ELECTRODE SYSTEM.
 NOTE:NEED FAULT CURRENT CACULATIONS
 FOR AIC RATING.215-5
 NOTE:NEED NEUTRAL COND. FROM METERCAN
 TO DISC.TO PANEL.
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.
 210-8-A-6/210-52C-1-2-3-4-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:REQ`MENTS FOR OUTLET SPACING 210-52