Plan Review Notes
Plan Review Notes For Permit 99050123
Permit Number 99050123
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-FOOTING F1 WAS NOT REVISED. SOIL TEST
 REPORT REQUIRED A FOOTING WIDTH OF 18"
 TO 34".
 2-CONNECTION OF A GARAGE WITH ANY ROOM
 WITH A GAS APPLIANCE SHALL BE BY MEANS
 OF A DOORWAY WITH A RAISED SILL AT
 LEAST 8" ABOVE THE GARAGE FLOOR.
 SECTION 411.2.7 SBC 1994.
 3-PROVIDE SPECIFICATIONS TO COMPLY WITH
 SECTION 402.7 SGC 1994 FOR INSTALLATION
 OF GAS APPLIANCES IN GARAGE.
 4-ENTRY DOORS TO BE 32" MINIMUM CLEAR.
 TABLE 1004 SBC 1994.
 5-SPECIFY SIZE OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE 1997
 AND AS PER CREDIT TAKEN IN ENERGY CALCS
 6-REVISE SPECIFICATION FOR INSULATION IN
 ATTIC. IT SHOULD BE R-30 AS PER ENERGY
 CALCULATIONS. SEE SHEET A5, SECTION AA.
 7-PROVIDE CONNECTION DETAILS. SEE SHEET
 FOR COMMENTS
 8-SEE COMMENTS ON ALL PLANS.
  
 NOTE:
 PLEASE CLOUD ALL REVISIONS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.