| Plan Review Notes For Permit 99050115 |
| Permit Number |
99050115 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | NEED TO SUBMIT FAULT CURRENT CALCS. | | | FOR AIC RATING WHICH NEEDS TO BE LISTED | | | ON PANEL SCHD.215-5 | | | NOTE:EQUIPMENT GROUNDING COND.REQ`D | | | FROM MAIN DISC. TO PANEL. | | | | | | NEED BEFORE ROUGH INSPECTION. |
|