Plan Review Notes
Plan Review Notes For Permit 99050113
Permit Number 99050113
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********UNSAT********************
  
 1)NOTE: NEED TO SUBMIT AIC RATING
 FIGURED FROM FAULT CURRENT CALCUULATIONS
 ARTS;110-9/215-5
 AIC RATING SHOULD BE LISTED ON ALL
 PANEL SCHEDULES FROM HERE ON OUT.
 2) NOTE:PLEASE INCLUDE EQUIPMENT GROUND
 AS REQ`D BY CODE FROM MAIN DISC.TO
 PANEL.SIZED FROM ART;250-95