| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT CIVIL DRWGS.AS NOTED ON SHT.P-1 |
| | THAT CLEARLY SHOW CONNECTION OF SANITARY |
| | AND WATER LINES TO CITY UTILITIES. |
| | SPC SEC.104.2.1,104.3.1. |
| | |
| | SHT.A-2 SHOWS ROOF DRAINS-SUBMIT STORM |
| | WATER RISER FOR REVIEW.SUPPLY SQ.FT.AREA |
| | DRAINED BY EACH DRAIN,PIPE SIZES,SLOPE |
| | OF PIPE,TERMINATION PT.,ETC. SPC.SEC. |
| | 1101.2.TYPE OF PIPING SHALL COMPLY W/SPC |
| | SEC.1103.4, 1104. |
| | |
| | SUBMIT PROVISIONS FOR SECONDARY DRAINAGE |
| | OF ROOF AREA WHERE ROOF DRAINS ARE |
| | LOCATED. SPC SEC.1109.1 |
| | |
| | SLOPE OF SANITARY SYSTEM SHALL COMPLY |
| | W/SPC SEC.705.2,705.3.(SEE NOTE #8 ON |
| | SHT.P.1.) |
| | |
| | SHT.P.1-NOTE #11-"M" COPPER NOT |
| | PERMITTED BELOW GROUND PER COUNTYWIDE |
| | AMENDMENTS SEC.611.3. |
| | |
| | SHT.P.1-NOTE #16 REFERS TO GAS.SUBMIT |
| | PLANS FOR GAS IF APPLICABLE.IF NO GAS |
| | DELETE NOTEFROM PLAN. |
| | |
| | SHT.P1-MIN.DISTANCE BETWEEN BUILDING |
| | DRAIN /SEWER AND WATER SERVICE SHALL |
| | COMPLY W/SPC SEC.608.3 |
| | |
| | CONDENSATE DRAINS SHALL DISCHARGE PER |
| | STD,MECH.CODE SEC.304.8.3 & COUNTYWIDE |
| | AMENDMENTS TO SPC.SEC.804.3. |
| | |
| | |
| | ****************PROVISO***************** |
| | SECONDARY DRAINAGE PROVISIONS SHALL BE |
| | PROVIDED FOR LOW ROOF AREA AND COMPLY W/ |
| | STANDARD BUILDING CODE SECS.1507.4.1, |
| | THRU 1507.4.3, 1604.6.2(1-4),AND |
| | STANDARD PLUMBING CODE SEC.1109.1, |
| | 1109.2, 1109.3. |
| | |
| | PLANS AND RISER DIAGRAM REQ'D.PRIOR TO |
| | RGH.PLBG.INSP.6/30/99. |