| Plan Review Notes For Permit 99050040 |
| Permit Number |
99050040 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | NOTE:PLANS SHOW MAIN DISCONNECTS, IF | | | MAIN DISC.ARE BEING USED THEN YOU | | | NEED TO DRAW ON RISER DIAGRAM.215-5 | | | NOTE:NEED RISER DIAGRAM FOR UNIT'A'. | | | ALL ABOVE TO INCLUDE CONDUITS,WIRE, | | | AND SIZES OF EACH. | | | NOTE:GROUNDING ELECTRODE CONDUCTOR TO | | | C.W.P. ALSO. | | | NOTE:MISSING SMOKE DETECTOR,NEED INSIDE | | | AND OUTSIDE BEDROOMS. | | | | | | NEED THE ABOVE INFORMATION BEFORE | | | ROUGH INSPECTION IS CALLED IN. |
|