| Plan Review Notes For Permit 99050037 |
| Permit Number |
99050037 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | NOTE:PLANS SHOW MAIN DISC. BEING USED. | | | IF SO THEN MAIN NEEDS TO BE INCLUDED | | | ON RISER DIAGRAM!215-5 | | | ALSO NEED GROUNDING ELECTRODE CONDUCTOR | | | TO GO TO C.W.P. | | | NOTE:KITCHEN OUTLET REQ`MENTS. | | | SERVING KIT.COUNTER TO BE GFI/GFI | | | PROTECTED.210-8-A-6 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | | | | NEED THE ABOVE INFORMATION BEFORE | | | ROUGH INSPECTION IS CALLED. |
|