| Plan Review Notes For Permit 99041328 |
| Permit Number |
99041328 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | NOTE:PRINT SHOWS MAIN DISC..IF SO THEN | | | NEEDS TO BE DRAWN ON RISER DIAGRAM!!! | | | ART.215-5 | | | NOTE:NEED FAULT CURRENT CALCULATIONS | | | FOR AIC RATING.215-5 | | | NOTE:GROUNDING ELECTRODE COND.TO GROUND | | | ROD AND BLDG.STEEL. | | | NOTE:210-8-A-6 REQ`MENTS FOR RECEPTS. | | | SERVING KITCHEN COUNTER TO BE GFI/OR | | | PROTECTED. | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:ART.210-52A OUTLET SPACING.2`6`12` | | | RULE. | | | | | | NEED CHANGES BEFORE ROUGH INSPECTION | | | IS CALLED IN!!!! |
|