| 2001-01-08 00:00:00 | ************DENIED********************** | | | APPROVED BY D. PALMER. SEE APPLICATION | | | NEED FAULT CURRENT CALCULATIONS FOR | | | AIC RATING.215-5 | | | NEED COMPLETE RISER DIAGRAM.!!! | | | SHOW CONDUIT SIZES,WIRE SIZES,GROUNDING | | | ELECTRODE SYSTEM TO INCLUDE GROUND ROD, | | | C.W.P,AND BLDG.STEEL. | | | NEED LOAD CACULATION FOR EACH PANEL! | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:WP GFI RECEPTS.REQ`D FOR A/C EQUIP. | | | ART.210-63 | | | NOTE:RECEPTS. LOCATED IN GARAGE ARE TO | | | BE GFI OR GFI PROTECTED UNLESS | | | DEICATED OUTLET.210-8-A-2 | | | NOTE:RECEPTS.REQ`D TO SERVE KITCHEN. | | | ART`S 210-8-A-6,210-52C-1-2-3-4-5 | | | NOTE:210-52A 2`6`12`RULE. |
|