Plan Review Notes
Plan Review Notes For Permit 99041302
Permit Number 99041302
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************DENIED**********************
 APPROVED BY D. PALMER. SEE APPLICATION
 NEED FAULT CURRENT CALCULATIONS FOR
 AIC RATING.215-5
 NEED COMPLETE RISER DIAGRAM.!!!
 SHOW CONDUIT SIZES,WIRE SIZES,GROUNDING
 ELECTRODE SYSTEM TO INCLUDE GROUND ROD,
 C.W.P,AND BLDG.STEEL.
 NEED LOAD CACULATION FOR EACH PANEL!
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:WP GFI RECEPTS.REQ`D FOR A/C EQUIP.
 ART.210-63
 NOTE:RECEPTS. LOCATED IN GARAGE ARE TO
 BE GFI OR GFI PROTECTED UNLESS
 DEICATED OUTLET.210-8-A-2
 NOTE:RECEPTS.REQ`D TO SERVE KITCHEN.
 ART`S 210-8-A-6,210-52C-1-2-3-4-5
 NOTE:210-52A 2`6`12`RULE.