| Plan Review Notes For Permit 99041284 |
| Permit Number |
99041284 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************PROVISO******************** | | | | | | NOTE:IF MAIN DISC. IS BEING INSTALLED | | | AS ON PLANS THEN PUT ON RISER DIAGRAM. | | | NOTE:GROUNDING ELECTRODE COND. TO | | | C.W.P ALSO. | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | | | | NEED THE ABOVE DONE BEFORE FINAL | | | INSPECTION IS CALLED IN. | | | OK`D 7/15/99 |
|