2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED NEUTRAL LOAD CALCULATIONS
 BEING THAT NEUTRAL COND.IS DOWNSIZED.
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO BLDG.STEEL ALSO.
 NOTE:REQ`D GFI RECEPT.210-63
 NOTE:2`6`12`RULE 210-52A
  
 NEED THE ABOVE INFORMATION BEFORE ROUGH
 INSPECTION IS CALLED IN.
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.215-5