| Plan Review Notes For Permit 99041258 |
| Permit Number |
99041258 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | NOTE:NEED NEUTRAL LOAD CALCULATIONS | | | BEING THAT NEUTRAL COND.IS DOWNSIZED. | | | NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO BLDG.STEEL ALSO. | | | NOTE:REQ`D GFI RECEPT.210-63 | | | NOTE:2`6`12`RULE 210-52A | | | | | | NEED THE ABOVE INFORMATION BEFORE ROUGH | | | INSPECTION IS CALLED IN. | | | NOTE:NEED FAULT CURRENT CALCULATIONS | | | FOR AIC RATING.215-5 |
|