| Plan Review Notes For Permit 99040966 |
| Permit Number |
99040966 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | 1) VENTILATION REQUIRED FOR OFFICE (TOOL | | | ROOM) BEHIND OFFICE #6 ASHRAE 62-89 | | | 2) AREAS WITH 300 CFM OR GREATER REQUIRE | | | R/A FROM AREA | | | 3) NO COMBUSTIBLES PERMITTED IN RETURN | | | AIR PLENUM INCLUDING PVC VENT MATERIAL | | | 4) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | PER 1994 SMC 406.1 WITH NOTIFICATION BY | | | HORN AND STROBE OR TIED TO BLDG FIRE | | | ALARM PER NFPA 90A 4-4.4.2 OR .3 |
|