| Plan Review Notes For Permit 99040858 |
| Permit Number |
99040858 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************DENIED***************** | | | | | | WHERES ELEC.?? | | | IF DOORS ARE THE ONLY THING BEING | | | ADDED THEN YOU NEED TO ADD SWITCH WITH | | | OUTSIDE LIGHT AS REQ`D BY CODE AS MEANS | | | OF EGRESS.ART:210-70 | | | ART:210-52A ALSO REQ`S RECEPTS.EVERY 2` | | | OF WALL,WITHIN 6`OF DOOR AND EVERY 12` | | | THERAFTER.D.V.P. | | | | | | 5/27/99/OWNER WILL ADD SWITCH AND LIGHTS | | | AS PER ART:210-70 D.V.P. |
|