2001-01-08 00:00:00***************PROVISO******************
  
 NEED FAULT CURRENT CALCULATIONS FOR
 AIC RATING.ART.215-5
 NED NEUTRAL LOAD CALCULATION SINCE
 WIRE IS BEING DOWNSIZED 2 TIMES.
 SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS
 NOTE:RECEPTS. SERVING KITCHEN COUNTER
 ARE TO BE GFI.ART.210-8-A-6
 NOTE: GROUNDING TO BLDG. STEEL ALSO.
  
 NEED ALL ABOVE INFORMATION BEFORE
 ROUGH INSPECTION IS CALLED.