| Plan Review Notes For Permit 99040823 |
| Permit Number |
99040823 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | WATER AND SANITARY RISER SHALL CORRELATE | | | W/PLAN VIEW,SIZE ALL SECTIONS OF SAN. | | | RISER.SPC SEC.104.2.1 | | | FIXTURE CLEARANCE OF W.C.SHALL COMPLY W/ | | | SPC SEC.403.4 | | | CLEANOUTS SHALL COMPLY W/SPC SEC.710.2.1 | | | & 710.2.3. | | | OPT.LAUNDRY TRAY NOT SHOWN ON SAN.OR | | | WATER RISER.SPC SEC.104.2.1 | | | INDICATE ON PLANS THAT PLBG.FIXTURES | | | COMPLY W/SPC TABLES 405 & 406. |
|