| Plan Review Notes For Permit 99040823 |
| Permit Number |
99040823 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | | | | NEED FAULT CURRENT CALCULAIONS FOR AIC | | | RATING.ART.215-5 | | | NOTE:REQ`MENTS FOR KITCHEN RECEPTS.AS | | | PER 210-8-A-6 | | | NOTE:ART.210-52H FOR MASTER HALL. | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NEED NEUTRAL CALCULATIONS SINCE THE WIRE | | | SIZE IS BEING DOWNSIZED. | | | NOTE:GROUNDING ELECTRODE SYSTEM TO BLDG. | | | STEEL ALSO. | | | | | | NEED THE ABOVE INFORMATION BEFORE FINAL | | | IS CALLED. |
|