2001-01-08 00:00:00**************PROVISO*******************
  
 NEED FAULT CURRENT CALCULAIONS FOR AIC
 RATING.ART.215-5
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.AS
 PER 210-8-A-6
 NOTE:ART.210-52H FOR MASTER HALL.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NEED NEUTRAL CALCULATIONS SINCE THE WIRE
 SIZE IS BEING DOWNSIZED.
 NOTE:GROUNDING ELECTRODE SYSTEM TO BLDG.
 STEEL ALSO.
  
 NEED THE ABOVE INFORMATION BEFORE FINAL
 IS CALLED.