2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.215-5
 NOTE:EQUIPMENT GROUNDING COND. REQ`D
 FROM DISC. TO PANEL.250-95
 NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS.
 NOTE:RECEPTS. SERVING KITCHEN COUNTER
 SPACE TO BE GFI/GFI PROTECTED.210-8-A-6
 NOTE:REECEPTS.REQ`D 210-52A/210-52H
  
 NEED AIC INFORMATION AND GROUND WIRE
 INFORMATION BEFORE ROUGH INSPECTION
 IS CALLED.