| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | NOTE:NEED FAULT CURRENT CALCULATIONS | | | FOR AIC RATING.215-5 | | | NOTE:EQUIPMENT GROUNDING COND. REQ`D | | | FROM DISC. TO PANEL.250-95 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE | | | AND OUTSIDE BEDROOMS. | | | NOTE:RECEPTS. SERVING KITCHEN COUNTER | | | SPACE TO BE GFI/GFI PROTECTED.210-8-A-6 | | | NOTE:REECEPTS.REQ`D 210-52A/210-52H | | | | | | NEED AIC INFORMATION AND GROUND WIRE | | | INFORMATION BEFORE ROUGH INSPECTION | | | IS CALLED. |
|