2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISC.TO PANEL.
 250-95
 NOTE:NEED FAULT CURRENT CALCULATIONS
 FOR AIC RATING.
 NOTE:ALL KICHEN RECEPTS,SERVING KITCHEN
 COUNTER IS TO BE GFI/GFI PROTECTED.
 ART.210-8