Plan Review Notes
Plan Review Notes For Permit 99040411
Permit Number 99040411
Review Stop P
Sequence Number 14
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 2 SUBMITTALS DATED 10-19-00
 RE: CANTILEVERED HANGERS TO SUPPORT
 SOVENT AIREATOR FITTING,IS NOT A
 ACCEPTABLE METHOD, SEE ATTACHED FROM
 SPC 94 SEC 310.1.1,310.2.1
  
 PLEASE SUBMIT INFORMATION AS STATED IN
 MEETING WITH STAFF FROM JPI AND
 MR KEN LOWERY KTD ENGINEERING ON THE
 JOB SITE 10-17-00 RE: HANGERS FOR THE
 SOVENT AIREATOR FITTING, TO USE A 4"
 RISER CLAMP ON EA FITTING WITH 2 3/8"
 RODS ATTACHED TO ABOVE DECK WITH
 FLUSH ANCHORS.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233