Plan Review Notes
Plan Review Notes For Permit 99040411
Permit Number 99040411
Review Stop P
Sequence Number 11
Notes
Date Text
2001-01-08 00:00:001)THE MATERIALS USED FOR THE SOVENT
 SYSTEM SHALL MEET THE STANDARDS AND
 SPECIFICATIONS LISTED IN TABLE 703 OF
 THE SPC.THE CERTIFICATE OF COMPLIANCE
 FROM S.E.SPECIALTY LISTS 3 STANDARDS
 THAT ARE NOT CONTAINED IN SPC TABLE 703.
 ONE BEING "CISMA"177-85.MY CONCERNS
 REGARDING THIS STANDARD ARE AS FOLLOWS:
  
 )WHAT DO THE LETTERS "CISMA"REPRESENT
 AND IS THIS A NATIONALLY RECOGNIZED
 ORGANIZATION WITH THE AUTHORITY TO
 ISSUE SUCH DOCUMENTATION? SPC SEC.303.1,
 303.2,303.3.PROVIDE SUPPLEMENTAL SUPPORT
 DOCUMENTATION ON THIS ISSUE.
  
 B)PAGE ONE OF"CISMA DESIGNATION 177-85"
 NOTES"FOR DESIGN AND INSTALLATION
 STANDARDS REFER TO "CAST IRON SOVENT
 DESIGN MANUAL NO.802.MANUAL 802 IS
 PROPRIETARY TO CONINE MANUFACTURING.
 HOW CAN YOU COMPLY W/THIS"DESIGNATION"
 IF YOU ARE NOT INSTALLING CONINE
 FITTINGS?
  
 C)THE SUBMIITED "DESIGNATION"REFERS TO
 TABLES AND FIGURES WHICH ARE NOT
 ENCLOSED AND THEREFORE RENDER THIS ITEM
 INCOMPLETE AND UNACCEPTABLE.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.YOU MUST
 SUBMIT DOCUMENTATION FROM A PROFESSIONAL
 ENGINEER SHOWING HOW YOU COMPLY WITH
 THIS "DESIGNATION"IF PROPERLY SUBMITTED,
 AND IF IT IS ACCEPTED BY THIS DEPARTMENT
  
 2)STANDARD ASTM-126 IS FOR VALVE
 PRESSURE RETAINING PARTS,PIPE FITTINGS
 AND FLANGES AND DOES NOT APPLY TO
 SOVENT PLUMBING SYSTEMS.
  
 3)ASME/ANSI B16.45-1987-PLEASE SUBMIT A
 COPY OF THIS STANDARD AND DOCUMENTATION
 FROM A PROFESSIONAL ENGINEER VERIFYING
 COMPLIANCE.ALTHOUGH THIS STANDARD IS NOT
 LISTED IN THE SPC THE BUILDING OFFICIAL
 HAS THE AUTHORITY TO APPROVE SUCH METHOD
 OR MATERIAL ACCORDING TO THE MODEL
 COUNTYWIDE AMENDMENTS TO THE STANDARD
 CODES,1997 EDITION ADMINISTRATIVE AND
 SECOND AMENDMENTS TO THE 1994 PLUMBING
 CODE.
  
 4)THE DESIGN MANUAL NO.101 FROM SOUTH-
 EASTERN SPECIALTY & MANUFACTURING CO.
 CONTAINS THE COVER OF DESIGN MANUAL NO.
 802 FROM CONINE MANUF.AND ALSO A DESIGN
 GUIDE FROM THE CONINE MANUAL.SUBMIT
 PROOF OF AUTHORIZATION FROM CONINE
 MANUF.ALLOWING USE OF THEIR DESIGN
 MANUAL WITH YOUR SYSTEM.
  
 5)REMOVE THE APPLICATION GUIDELINES FOR
 A SPLIT SYSTEM AIR CONDITIONING SYSTEM
 FROM THE SOUTHEASTERN DESIGN MANUAL NO.
 101.THIS IS NOT APPLICABLE.
  
 6)THE LETTER FROM JIM STAHL DATED
 8/28/00 REFERS TO A CAST IRON SOVENT
 SYSTEM WHICH THIS IS NOT.IT IS A HYBRID
 SYSTEM CONSISTING OF PVC AND CAST IRON.
 THE FIRE SAFING DETAILS DO NOT ADDRESS
 PVC PIPING,THEREFORE THIS SYSTEM IS
 UNACCEPTABLE.COUNTYWIDE AMENDMENTS TO
 SBC SEC.104.2.4.
  
 7)DOCUMENTATION AND TEST RESULTS SHALL
 BE SUBMITTED FROM A PROFESSIONAL
 ENGINEER CLEARLY SHOWING HOW THE SOVENT
 FITTINGS MANUFACTURED BY SOUTHEASTERN
 SPECIALTY COMPLY W/CISPI STANDARD 301-82
 AND APPLICABLE STANDARDS REFERENCED IN
 TABLE 703 OF THE STANDARD PLUMBING CODE.
 THE CERTIFICATE OF COMPLIANCE FROM THE
 VICE PRESIDENT OF SOUTHEASTERN
 SPECIALTY IS UNACCEPTABLE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER