| Plan Review Notes For Permit 99040411 |
| Permit Number |
99040411 |
|
| Review Stop |
P |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLBG PLAN REVIEW OF SINGLE STACK | | | PLUMBING SYSTEM | | | (1) SHT P1.5 NOTE I PROVIDE CUT SHT FOR | | | PVC TO CI NO HUB BAND, THAT IS LISTED | | | FOR A TRANSITION OF CI TO PVC PIPE. | | | (2) SHTP1.5 PROVIDE A CUT SHT OF THE | | | UNDERFLOOR CLAMP MODEL #USC 886 TO | | | SUPPORT AERATOR FTG.AND HOW THIS IS TO | | | BE ANCHORED IN CONCRETE. | | | (3) SHT P1.5 PROVIDE A CUT SHT OF THE | | | INSTALLATION OF THE PRO-SET BOX P4542HEZ | | | 4" SOVENT BOX. | | | (4) SHT P1.5 NOTE # 8 SOVENT FITTING | | | MANFACTURE STANDARD, PROVIDE INFORMATION | | | ON CISMA DESIGNATION 177-85, STANDARD. | | | (5) SHT PI.6 RISER 1-S & 5-S,CONNECTION | | | OF SOIL OR WASTE BRANCHES BETWEEN THE | | | PRL & THE STACK,SHALL BE MORE THAN 10 | | | PIPE DIAMETERS DOWN STREAM OF THE STACK. | | | END OF COMMENTS,QUESTONS,CONTACT | | | PAUL SCHMITZ 561-659-8096 X 8233 |
|