Plan Review Notes
Plan Review Notes For Permit 99040411
Permit Number 99040411
Review Stop P
Sequence Number 10
Notes
Date Text
2001-01-08 00:00:00PLBG PLAN REVIEW OF SINGLE STACK
 PLUMBING SYSTEM
 (1) SHT P1.5 NOTE I PROVIDE CUT SHT FOR
 PVC TO CI NO HUB BAND, THAT IS LISTED
 FOR A TRANSITION OF CI TO PVC PIPE.
 (2) SHTP1.5 PROVIDE A CUT SHT OF THE
 UNDERFLOOR CLAMP MODEL #USC 886 TO
 SUPPORT AERATOR FTG.AND HOW THIS IS TO
 BE ANCHORED IN CONCRETE.
 (3) SHT P1.5 PROVIDE A CUT SHT OF THE
 INSTALLATION OF THE PRO-SET BOX P4542HEZ
 4" SOVENT BOX.
 (4) SHT P1.5 NOTE # 8 SOVENT FITTING
 MANFACTURE STANDARD, PROVIDE INFORMATION
 ON CISMA DESIGNATION 177-85, STANDARD.
 (5) SHT PI.6 RISER 1-S & 5-S,CONNECTION
 OF SOIL OR WASTE BRANCHES BETWEEN THE
 PRL & THE STACK,SHALL BE MORE THAN 10
 PIPE DIAMETERS DOWN STREAM OF THE STACK.
 END OF COMMENTS,QUESTONS,CONTACT
 PAUL SCHMITZ 561-659-8096 X 8233