2001-07-19 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE THAT THESE NOTES ARE IN
 RESPONSE TO LETTER FROM MR. GEORGE PEREZ
  
  
 1)NOTE: RESPONSE TO NOTE#2 PLEASE NOTE
 THAT NO PANEL SCHEDULES WERE SUBMITTED??
 PLEASE ALSO NOTE THAT THERE IS NOTHING
 IN THE NEC OR LOCAL AMENDMENTS THAT DOES
 NOT ALLOW #14AWG IN COMMERCIAL BLDG`S.
  
 2)NOTE: IN RESPONSE TO NOTE #5 PLEASE
 NOTE THAT HABITABLE ROOMS NEED TO SHOW
 LIGHT FIXTURES. SOME ROOMS IN APTS STILL
 SHOW "JB'S" WHER LTS SHOULD BE SHOWN.
 210-70
  
 3)NOTE: IN RESPONSE TO NOTE# 6. NO PANEL
 SCHEDULES??
  
 4)NOTE: IN REPSONSE TO NOTE #8; FIRST
 SET OF NOTES REFER TO LOCAL AMENDMENT
 210-50 REQ`S OUTLETS EVERY 20`.
  
 5)NOTE: IN RESPONSE TO NOTE# 6; PLEASE
 NOTE THAT NO BRANCH CIRCUIT #`S ARE
 SHOWN ON PLANS AND NO PANEL SCHEDULE TO
 CORRELATE? PLEASE SUBMIT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  