| Plan Review Notes For Permit 99040392 |
| Permit Number |
99040392 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-07-19 00:00:00 | ***************** UNSAT *************** | | | | | | PLEASE NOTE THAT THESE NOTES ARE IN | | | RESPONSE TO LETTER FROM MR. GEORGE PEREZ | | | | | | | | | 1)NOTE: RESPONSE TO NOTE#2 PLEASE NOTE | | | THAT NO PANEL SCHEDULES WERE SUBMITTED?? | | | PLEASE ALSO NOTE THAT THERE IS NOTHING | | | IN THE NEC OR LOCAL AMENDMENTS THAT DOES | | | NOT ALLOW #14AWG IN COMMERCIAL BLDG`S. | | | | | | 2)NOTE: IN RESPONSE TO NOTE #5 PLEASE | | | NOTE THAT HABITABLE ROOMS NEED TO SHOW | | | LIGHT FIXTURES. SOME ROOMS IN APTS STILL | | | SHOW "JB'S" WHER LTS SHOULD BE SHOWN. | | | 210-70 | | | | | | 3)NOTE: IN RESPONSE TO NOTE# 6. NO PANEL | | | SCHEDULES?? | | | | | | 4)NOTE: IN REPSONSE TO NOTE #8; FIRST | | | SET OF NOTES REFER TO LOCAL AMENDMENT | | | 210-50 REQ`S OUTLETS EVERY 20`. | | | | | | 5)NOTE: IN RESPONSE TO NOTE# 6; PLEASE | | | NOTE THAT NO BRANCH CIRCUIT #`S ARE | | | SHOWN ON PLANS AND NO PANEL SCHEDULE TO | | | CORRELATE? PLEASE SUBMIT. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|