| Date |
Text |
| 2001-03-13 00:00:00 | ****************UNSAT ***************** |
| | |
| | PLEASE NOTE: ELECTRCIAL PLANS ARE JUST |
| | NOW BEING SUBMIITED FOR REVIEW. PLEASE |
| | SEE THE FOLLOWING NOTES. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. FOR ALL APTS. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. PLEASE SHOW |
| | CLARIFICATION. |
| | |
| | 5) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | YOU SHOW JB IN LOCATIONS OF WHICH MEANS |
| | OF EGRESS LIGHTING IS REQ`D. |
| | |
| | 6)NOTE: PLANS NEED TO SHOW ALL BRANCH |
| | CIRCUIT #`S ON PLANS. THESE NEED TO |
| | CORRELATE WITH PANEL SCHEDULES. NEED TO |
| | SUBMIT PANEL SCHEDULES FOR ALL PANELS. |
| | PLANS ARE COMING IN AS "AS-BUILTS" ?? |
| | |
| | 7)NOTE: PLEASE NOTE PER 210-8 RECEPTS |
| | SHOWN IN BATHROOMS DOWNSTAIRS NEED TO |
| | BE SHOWN AS GFI/GFI PROTECTED. |
| | |
| | 8)NOTE: PLEASE NOTE OUTLET SPACING TO |
| | MEET LOCAL AMENDMENTS OF ART 210-50. |
| | UPSTAIRS HALLWAYS. |
| | |
| | 9)NOTE: PLEASE SHOW LOCATIONS OF AHU`S. |
| | |
| | 11)NOTE:PLEASE LABEL APARTMENTS ON E- |
| | SHEETS. |
| | |
| | 12)NOTE: PLEASE SEE TWO SWITCHES IN |
| | REARAPT IN BEDROOM? GOING TO ??? |
| | |
| | 13)NOTE: PLEASE SEE 553-79-6A F.A.C. |
| | REQUIRES SERVICES ON COMMERCIAL |
| | PRODJECTS OF 800A OR MORE TO BE SIGNED |
| | AND SEALED BY AN ENGINEER PER 471.025 |
| | |
| | PLEASE ADDRESS ALL OF THE ABOVE COMMENTS |
| | AND SUBMIT FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS PERTAINING TO ANY OF THE ABOVE |
| | PLEASE CALL FOR CLARIFICATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |