| Plan Review Notes For Permit 99040392 |
| Permit Number |
99040392 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1) NO OUTSIDE AIR CALCULATIONS SHOWN PER | | | ASHRAE 62-89 | | | 2) 2ND FL APTS A/CSUPPLY SHALL NOT | | | SERVE THE COMMON CORRIDOR PER 1994 SMC | | | 609.1.1 | | | 3) PROVIDE INFORMATION ON BATHROOM EX- | | | HAUST FANS AND VENT DUCT FOR THE SECOND | | | FLOOR | | | 4) DRYER VENT TO COMPLY WITH 1994 SMC | | | 509.1, 509.2 AND 509.4 COMMERCIAL EX- | | | HAUST AND SHALL NOT BE IN RATED WALL |
|