| Plan Review Notes For Permit 99040226 |
| Permit Number |
99040226 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************DENIED******************* | | | | | | NEED CORRECT RISER DIAGRAM WITH CORRECT | | | WIRE SIZES. | | | NEED FAULT CURRENT CALCULATIONS FOR AIC | | | RATING. | | | PANEL SHD.NOTES #14 WIRE FOR SMALL APP. | | | CIRCUTS IN KITCHEN.MUST BE #12 ON A | | | 20AMP CIRCUT. | | | NEED TO SHOW CORRECT GROUNDING METHOD.! | | | NOTE:RECEPTS.SERVING KITCHEN COUNTER | | | ARE TO BE GFI. | | | NOTE:KITCHEN PENINSULAR RECEPT.REQ`MENTS | | | NOTE: OTHER RECEPTS.REQ`D IN THE HOUSE. | | | PLEASE HAVE ALL RESUBMITTED!!!!!!! |
|