2001-01-08 00:00:00***************DENIED*******************
  
 NEED CORRECT RISER DIAGRAM WITH CORRECT
 WIRE SIZES.
 NEED FAULT CURRENT CALCULATIONS FOR AIC
 RATING.
 PANEL SHD.NOTES #14 WIRE FOR SMALL APP.
 CIRCUTS IN KITCHEN.MUST BE #12 ON A
 20AMP CIRCUT.
 NEED TO SHOW CORRECT GROUNDING METHOD.!
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 ARE TO BE GFI.
 NOTE:KITCHEN PENINSULAR RECEPT.REQ`MENTS
 NOTE: OTHER RECEPTS.REQ`D IN THE HOUSE.
 PLEASE HAVE ALL RESUBMITTED!!!!!!!