| Plan Review Notes For Permit 99040125 |
| Permit Number |
99040125 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT********************* | | | | | | NOTE:STILL NEED AIC RATING OF EQUIPMENT | | | FROM FAULT CURRENT CALCULATIONS. | | | NOTE:STILL NEED TO HAVE GROUNDING ELEC. | | | CONDUCTOR TO GO TO BLDG.STEEL. | | | NOTE:DEDICATED CIRCUTS FOR GARAGE DOOR | | | OPENERS NOT ON LOAD CALCULATIONS. | | | CHANGE FOR SECOND FLOOR IS O.K.`D | | | NEED THE ABOVE INFORMATION BEFORE ROUGH | | | INSPECTION IS CALLED. |
|