| Plan Review Notes For Permit 99040095 |
| Permit Number |
99040095 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | | | | SHEET A,NEED FAULT CURRENT CALCULATIONS. | | | NEED AIC RATING TO BE LISTED ON PANEL. | | | ART 215-5 | | | NOTE:PG.2OF6 ALL RECEPTS SERVING KITCHEN | | | COUNTER MUST BE GFI OR GFI PROTECTED. | | | ART:210-8-A-6 | | | NOTE:PG. 2OF6 REC.REQ`D WITHIN 6' | | | OF DOOR.ART.210-52A | | | NOTE:PG.3OF6 SMOKE DETECTORS REQ`D | | | INSIDE AND OUTSIDE BEDROOMS. | | | NOTE:PG.3OF6 RECEPTS.REQ`D IN HALLWAYS | | | ART.210-52H | | | NOTE:PG.3OF6 RECEPTS. REQ`D 2'OF WALL | | | ART.210-52A | | | NEED CHANGES TO BE MADE BEFORE ROUGH | | | INSPECTION IS CALLED IN. |
|