| Plan Review Notes For Permit 99031607 |
| Permit Number |
99031607 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | EXISTING DUCT TO BE INSPECTED FOR CLEAN- | | | LINESS AND IF DEEMED NECESSARY CLEANED | | | AND SANITIZED BY LICENSED MECHANICAL | | | CONTRACTOR | | | 2)FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | PER 1994 SMC 406.1 | | | 3)NOTIFICATION REQUIRED PER NFPA 90A 4-4 | | | .4.3 BY HORN AND STROBE |
|