| 2001-01-08 00:00:00 | *****************DENIED**************** | | | NEED TO GIVE MORE DETAILED INFORMATION | | | ON ALL ELECTRICAL.DRAW IN SWITCH LEGS | | | SMOKE DETECTORS REQ`D INSIDE AND OUTSIDE | | | BEDROOMS. | | | LIGHTS REQ`D BY 210-70 AT MEANS OF | | | EGRESS. | | | NOTE:210-8-A-6 RECEPTS.SERVING KITCHEN | | | COUNTER SPACE. | | | YOU SHOW 6-GANG BOX BUT ONLY SHOW ONE | | | SWITCH. | | | ALSO PLEASE HAVE ELECTRICAL RISER | | | DIAGRAM AND LOAD CALCULATIONS DRAWN | | | ON SAME PAGE. | | | PLEASE DRAW IN NEW PANEL SCHED.WITH | | | AIC RATING OF EQUIPMENT. | | | 215-5 |
|