| Plan Review Notes For Permit 99031452 |
| Permit Number |
99031452 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1) OUTSIDE AIR CALCS SHOW 4 PEOPLE OCCUP | | | ANCY, AND THE ENERGY CALCS SHOW 21PEOPLE | | | ADJUST OUTSIDE AIR TO REFLECT CORRECT | | | OCCUPANCY. | | | 2) DRYER VENT LENGTH NOT TO EXCEED 25' | | | TOTAL, INCLUDING 5' DEDUCTION FOR EACH | | | 90 DEGREE BEND, UNLESS MANUFACTURES SPEC | | | SUPPLIED FOR DRYER TO BE INSTALLED PRIOR | | | TO FINAL C/O | | | 3)IF RETURN AIR IS THROUGH ABOVE CEILING | | | PLENUM, NO COMBUSTIBLES ALLOWED IN | | | PLENUM(ABOVE CEILING) |
|