Plan Review Notes
Plan Review Notes For Permit 99031032
Permit Number 99031032
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED SEE CHECK LIST 5/18/99
  
 NEEDED FAULT CURRENT CALCULATIONS AND
 AIC RATING FIRST TIME.DID NOT RECEIVE.
 NOTE:STILL NEED CACULATIONS AND AIC
 RATING LISTED ON PLANS.
 NOTE:EQUIP.GRONDING COND.REQ`D 250-95
 NOTE:MISSING RECEPTS.ART.210-52A
  
 ******NEED ABOVE INFORMATION BEFORE
 FINAL INSPECTION.!!!!!!!!!