| 2001-01-08 00:00:00 | SECOND CHECKLIST: |
| | 1-PROVIDE 2 COPIES OF ENERGY CALCULATION |
| | AND MANUAL "J" CALCULATIONS. |
| | 2-PROVIDE ADEQUATE LIGHT AND VENTILATION |
| | AT MASTER BEDROOM AND LIVING AREA. |
| | SEC. 1203.1 AND 1203.1.4 SBC 1994. |
| | 3-PROVIDE THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS. SEC. 1606 SBC 1994. |
| | 4-SPECIFY/CLARIFY HURRICANE TRUSS ANCHOR |
| | AT EXISTING WALL. CONNECTOR SPECIFIED, |
| | SIMPSON LTS 18, IS A WOOD TO WOOD |
| | CONNECTOR BUT THE CONNECTOR REQUIRED IS |
| | A WOOD TO CONCRETE BEAM. |
| | 5-PROVIDE TWO COPIES OF CURRENT PRODUCT |
| | APPROVAL FOR: ALL EXTERIOR DOORS AND |
| | WINDOWS, STORM SHUTTERS, ROOF SHINGLES. |
| | 6-PROVIDE ROOF SHEATHING FASTENING |
| | SPECIFICATIONS. TABLE 2306.1 CITY |
| | AMENDMENTS TO SBC 1994. |
| | 7-PROVIDE COMPLETE COLUMN/SECTION DETAIL |
| | CLEARLY SPECIFY THE TOP PLATE SIZE AND |
| | BOLTS. INCLUDING CORNER COLUMN. |
| | *SPECIFY COLUMN TO BE USED.INCLUDING |
| | THICKNESS. |
| | *CLARIFY INSTALLATION OF COLUMN AT BASE |
| | AND PROVIDE UPLIFT CALCULATIONS. |
| | 8-IDENTIFY LOCATION AND DIMENSIONS OF |
| | EACH SHEAR WALL SEGMENT AND SPECIFY |
| | ANCHORING AT EACH END. |
| | *SPECIFY SPECIAL ANCHORING AT CORNERS. |
| | SEC. 2310 SBC 1994. |
| | 9-PROVIDE NAME AND ADDRESS OF ENGINEER |
| | OF RECORD OR ENGINEER'S BUSINESS LOGO. |
| | SEC. 104.2.2 CITY AMENDMENTS. |
| | 10-*PAY IMPACT FEES TO THE COUNTY. |
| | *PAY ADDITIONAL FEES TO THE CITY |
| | $479.49 FOR RADON FEES & VALUATION |
| | 11-PROVIDE SIZE AND REINFORCEMENT FOR |
| | CONCRETE EDGE AT REAR PORCH SLAB. |
| | 12-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | CONSTRUCTION OF CEILING AT REAR PORCH |
| | AS PER SEC. 2504.2 SBC 1994 (ASTM C926 |
| | AND ASTM C1063). |
| | NOTE:SEE COMMENTS ON PLANS & MECHANICAL |
| | PLAN EXAMINER CHECKLIST. |