Plan Review Notes
Plan Review Notes For Permit 99030754
Permit Number 99030754
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:RISER DIAGRAM SHOWS 2#4`S PLEASE
 CORRECT AS #4 IS NOT RATED FOR 150AMPS
 ART:310-16
 2)NOTE:RISER DIAGRAM SHOWS 4/0 FOR GRND-
 ING ELECTRODE CONDUCTOR IN 1/2" CONDUIT.
 ALSO NEEDS TO SHOW GOING TO CWP AND
 BLDG.STEEL.250-81
 3)NOTE:MASTER BATH RECEPTS. TO BE GFI
 AND 20 AMP BRANCH CIRCUT ART210-52D
 4)NOTE:WP GFI REQ`D FOR A/C COND.UNIT
 AS PER ART: 210-63
 5)NOTE:MASTER BEDROOM MISSING RECEPT.
 AT DOOR REQ`D BY ART: 210-52
 6)NOTE: ART:210-8-A-6 REQ`SALL RECEPTS.
 SERVING KITCHEN COUNTER TO BE GFI AS PER
 NEC.
 7)NOTE:PANEL SCHEDULE SHOWS SMALL APPLI-
 -ANCE CIRCUT WITH #14 AWG.SMALL APPLI-
 -ANCE ARE REQ`D TO BE 20AMP THEREFORE
 WIRE NEEDS TO BE #12.ART:310-16
 NOTE OTHER CIRCUTS THAT ARE BEING
 PROTECTED BY 20AMP BRKS.ON #14 AWG.
 NEED TO CHANGE WIRE OR OVERCURRENT
 POTECTION.
  
 PLEASE NOTE THAT ALL THE ABOVE CHANGES
 NEED TO BE SUBMITTED AND APPROVED BEFORE
 FIRST ELECTRICAL ROUGH INSPECTION.