| Plan Review Notes For Permit 99030754 |
| Permit Number |
99030754 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | 1)NOTE:RISER DIAGRAM SHOWS 2#4`S PLEASE | | | CORRECT AS #4 IS NOT RATED FOR 150AMPS | | | ART:310-16 | | | 2)NOTE:RISER DIAGRAM SHOWS 4/0 FOR GRND- | | | ING ELECTRODE CONDUCTOR IN 1/2" CONDUIT. | | | ALSO NEEDS TO SHOW GOING TO CWP AND | | | BLDG.STEEL.250-81 | | | 3)NOTE:MASTER BATH RECEPTS. TO BE GFI | | | AND 20 AMP BRANCH CIRCUT ART210-52D | | | 4)NOTE:WP GFI REQ`D FOR A/C COND.UNIT | | | AS PER ART: 210-63 | | | 5)NOTE:MASTER BEDROOM MISSING RECEPT. | | | AT DOOR REQ`D BY ART: 210-52 | | | 6)NOTE: ART:210-8-A-6 REQ`SALL RECEPTS. | | | SERVING KITCHEN COUNTER TO BE GFI AS PER | | | NEC. | | | 7)NOTE:PANEL SCHEDULE SHOWS SMALL APPLI- | | | -ANCE CIRCUT WITH #14 AWG.SMALL APPLI- | | | -ANCE ARE REQ`D TO BE 20AMP THEREFORE | | | WIRE NEEDS TO BE #12.ART:310-16 | | | NOTE OTHER CIRCUTS THAT ARE BEING | | | PROTECTED BY 20AMP BRKS.ON #14 AWG. | | | NEED TO CHANGE WIRE OR OVERCURRENT | | | POTECTION. | | | | | | PLEASE NOTE THAT ALL THE ABOVE CHANGES | | | NEED TO BE SUBMITTED AND APPROVED BEFORE | | | FIRST ELECTRICAL ROUGH INSPECTION. |
|